Voltage Drop Calculator

Calculate voltage drop, receiving voltage, and wire loss for single-phase, three-phase, and DC circuits, then compare nearby AWG and kcmil sizes.

Last updated: 2026/03/28

Voltage Drop Calculator

Estimate voltage drop (V), voltage drop (%), receiving-end voltage, and conductor loss for single-phase AC, three-phase AC, and DC circuits. Enter current, voltage, one-way length, conductor material, and wire size to compare the current setup against common 3% and 5% planning targets.

Calculation inputs
V
A
ft

Enter one-way length in feet. The calculator automatically handles round-trip distance for single-phase and DC circuits.

PF

This is a resistance-focused planning estimate. Long feeders, large motors, and reactive loads should still be checked against your project standard.

Quick presets
Quick planning notes
  • 3% is a common planning target for branch circuits, while 5% is often used as a whole-run target.
  • Enter one-way length in feet. The calculator automatically handles round-trip distance for single-phase and DC circuits.
  • Copper and aluminum produce different results because their resistivity is different.
  • Power factor only affects AC modes. DC is always treated as PF = 1.
  • This tool uses 20°C conductor resistivity for planning. Final design checks should still follow your local code, equipment limits, and cable data tables.
Check the inputs.

Enter positive values for voltage, current, one-way length, and wire size to update the results.

Estimated voltage drop

Current setup voltage drop and receiving-end voltage

V

After you calculate, the drop percentage, receiving voltage, and suggested wire sizes will appear here.

Not calculated Use the 3% and 5% markers as planning targets when you compare nearby wire sizes.
Voltage drop –%

This is the percentage drop relative to nominal voltage.

Receiving voltage — V

Estimated voltage at the load end.

Conductor loss — W

Approximate I²R heat loss for the selected run.

Suggested wire size 3% target: —5% target: —

The resistance summary will appear here.

Nearby wire-size comparison

Compare the selected wire size with nearby AWG or kcmil options under the same load conditions. Shorter bars mean less voltage drop.

Wire-size comparison table

Review voltage drop, percent drop, receiving voltage, and the 3% / 5% planning check in one place.
Wire size Voltage drop Voltage drop % Receiving voltage Status
Results will appear here after you calculate.
This calculator uses 20°C resistivity values (Cu 0.017241 Ω·mm²/m, Al 0.028264 Ω·mm²/m) and a resistance-focused planning formula. Final design work should still follow the applicable code, temperature correction, cable installation method, and manufacturer data.

What is a voltage drop calculator?

A voltage drop calculator estimates how much voltage is lost as current travels through a conductor. Enter the system type, nominal voltage, load current, one-way length, conductor material, and wire size to estimate receiving-end voltage, conductor loss, and whether the current wire size is close to common 3% or 5% planning targets.

This is especially useful for longer branch circuits, feeder runs, and low-voltage DC wiring where even a small voltage drop can affect motors, controls, lighting, or battery-powered equipment.

When to use it

This tool is designed for quick planning checks before you open a full code table or project standard.

  • 120V branch circuits – Check whether a longer homerun still stays near common planning targets.
  • 208V / 480V three-phase runs – Review whether a feeder or equipment branch looks reasonable before final sizing.
  • 24V / 48V DC systems – Estimate voltage loss in controls, battery banks, solar accessories, or telecom-style wiring.
  • Copper vs aluminum – See how conductor material changes the result under the same load.
  • Wire-size upgrades – Compare nearby AWG or kcmil sizes to see when the drop becomes more comfortable.

Key features

The calculator gives you more than a single number so you can make a faster planning decision.

  • Single-phase, three-phase, and DC modes – Switch between common circuit types without leaving the page.
  • AWG and kcmil size choices – Use wire labels that match common US planning workflows.
  • Receiving voltage and conductor loss – See the practical impact of the chosen wire size, not just the percentage drop.
  • 3% and 5% planning targets – Quickly see what nearby size gets you under each target.
  • Nearby-size comparison chart and table – Compare several likely alternatives side by side.
  • Copy results – Send a quick text summary to a project note, email, or field discussion.

How to use it

Select the circuit type, then enter nominal voltage, load current, one-way length, conductor material, and wire size. For AC circuits, add a realistic power factor if you are checking a motor or another reactive load.

  1. Pick the system type – Single-phase AC, three-phase AC, or DC.
  2. Enter voltage, current, and one-way length – Length is entered in feet.
  3. Select conductor material and wire size – Copper and aluminum will produce different results.
  4. Enter power factor for AC – Use a conservative PF when you are checking motor or equipment loads.
  5. Read the result panel and comparison table – Start with the current size, then review the nearby options.

How the estimate works

This tool uses 20°C conductor resistivity to estimate resistance. Copper uses 0.017241 Ω·mm²/m and aluminum uses 0.028264 Ω·mm²/m. Conductor resistance is estimated with R = ρ × L ÷ A, where L is one-way length converted from feet to meters and A is the nominal conductor area behind the selected AWG or kcmil label.

The planning formulas are simplified as DC: ΔV = 2 × I × ρ × L ÷ A, single-phase AC: ΔV ≈ 2 × I × ρ × L ÷ A × PF, and three-phase AC: ΔV ≈ √3 × I × ρ × L ÷ A × PF. These are fast planning formulas, not a full impedance model.

Many US designers use 3% and 5% as planning targets, but final design work still depends on your code path, equipment tolerance, temperature correction, conductor installation method, and any project-specific engineering standard.

Frequently asked questions

Should I enter one-way length or round-trip length?

Enter one-way length. The calculator automatically handles round-trip distance for single-phase AC and DC circuits, while the three-phase mode uses the common three-phase planning factor.

Why does the DC mode ignore power factor?

Power factor is an AC concept. DC mode always uses a power factor of 1 because reactive AC effects are not part of the model.

Why does aluminum usually need a larger size?

Aluminum has a higher resistivity than copper, so the same run length and the same cross-sectional area will usually produce a larger voltage drop and more conductor loss.

How should I use the 3% and 5% results?

Treat them as planning targets, not automatic approval. Many branch-circuit discussions use 3% and many whole-run discussions use 5%, but your final check should still match the applicable code and project standard.

Can I use this as a final design calculation?

No. Use it for planning and quick comparisons, then confirm the final result with the relevant code tables, temperature correction, conductor installation method, and any required engineering review.

Why might a code table give me a different answer?

Code tables and manufacturer data may include additional impedance effects, temperature assumptions, conductor construction differences, or installation conditions that a fast planning calculator does not model.

Anonymous Opinion 1

Comments that may inconvenience others or repeat the same message can be hidden or removed under our moderation guidelines.

Characters left: 120

No comments yet. Leave the first opinion.